xPIPE


---

Application Scope

For enclosure power and communication electrical equipment:
- Control cabinets
- Transformers and relay equipment
- Backup power units
- Voltage converters
- Server racks and telephone exchanges

Packaging: Cardboard box
Service life: 60 months from manufacture date

Technical Parameters

| Model | AUP 100 | AUP 300 | AUP 500 | AUP 1K | AUP 1K5 | AUP 2K |
|---|---|---|---|---|---|---|
| Equipment enclosure volume (L) | 100 | 300 | 500 | 1000 | 1500 | 2000 |
| Extinguishing agent container size (mm) | 100x25x25 | 185x32x32 | 200x40x40 | 400x40x40 | 450x40x40 | 500x50x50 |
| Sensor tube length (mm) | 500 | 1000 | 1500 | 2000 | 2500 | 3000 |
| Minimum sensor tube bend radius (mm) | 40 | - | - | - | - | - |

Weight (g): 120 | 150 | 200 | 300 | 450 | 950
Extinguishing agent: Halon 227ea, Halon 318c, Perfluoroketone PK-49 (Novec 1230)
Operating temperature: -50°C to +65°C
Activation temperature: 125-145°C
Housing materials: Radiation-crosslinked polyethylene, polypropylene

Problem Relevance

Electrical equipment faults remain a leading cause of fires. Daily consequences include:
- 41,564 fires caused by electrical equipment violations (28% of all fires)
- 1,578 fatalities
- 14,500 destroyed buildings
- 12.09 billion RUB direct damage

Use strictly as intended. Certified product.

---

Intelligent Fire Protection

Description
Automatic fire suppression systems (AUP) XP/PE are designed for extinguishing fires in enclosure power and communication equipment (100-2000L capacity). The system consists of a cylinder with liquefied gas extinguishing agent and a fusible sensor tube.

Operation Principle
The cylinder mounts inside equipment while the sensor tube routes through high-risk areas. During fire:
1. Sensor tube melts
2. Released gas displaces oxygen
3. Temperature drops at fire source
4. Combustion process inhibited

Safety Features
- No organic solvents
- Non-toxic components
- Chemically inert gas - non-corrosive
- No equipment cleaning required post-use
- Explosion-proof agent container

Advantages
- Protects high-risk components (power supplies, high-current parts, contactors, relays)
- Ultra-fast detection and suppression
- Autonomous or automatic operation
- Compatible with fire alarm systems
- Optional pressure/level sensors
- Clean agent safe for electronics/optics
- Custom extinguishing agent selection
- Maintenance-free

---

System Components
1. Gas displacer
2. Extinguishing agent cylinder
3. Rupture disc
4. Thermal fuse element

Use strictly as intended. Certified product.

---

Made on
Tilda